The PS100 series modular, true online double conversion transformer-less design with 3-Level IGBT Inverter topology UPS ranging from 100kVA to 1200kVA is designed to protect any critical load for medium and large data center achieving maximum availability. The PS100 series feature the latest technology of DSP Microprocessor based control, using IGBT devices, high switching frequency PWM and PFC input control & Input Phase Sequence Correction, which guarantees ultra high efficiency of 97.1% and reliability. Its compact design ensures power density of 1200kVA in one cabinet, 6 units can be paralleled for capacity expansion or redundancy up to 7200kVA, making it an excellent choice for medium and large data centre.
SPECIFICATION OF MODULE | |
MODULE | PS100M33100 |
Dimension WxDxH (mm) | 440 x 755 x 130 (3U) |
Weight (Kg) Each 100kVA | 52.5 Kg |
INPUT | |
Nominal Voltage | 380V / 400V / 415V AC (3Ph+N+PE) |
Operating Voltage Range | 138V ~ 322V AC for 40% Load & 323V ~ 485V AC for 100% Load |
Operating Frequency Range | 40Hz ~ 70Hz Auto Sensing |
Power Factor | ≥ 0.99 |
Harmonic Distortion (THDi) | ≤ 3% |
Generator Input / Walking | Support / 0~40 Sec. (Configurable) |
OUTPUT | |
Output Voltage | 380V / 400V / 415V AC (3Ph+N+PE) |
Voltage Regulation | ± 1% |
Power Factor | 1.0 (Unity) |
Frequency | Auto Sensing 50 / 60 Hz ± 3Hz Sync Mode (Configurable), 50/60 Hz ± 0.1 Hz (Free Running / Self Clocked Mode) |
Crest Factor | 3:1 |
Harmonic Distortion (THDv) | ≤ 1% |
Over Load | ≤110% for 60 min, ≤125 % for 10 min, ≤ 150% for 1 min, > 150% for 200 ms |
Slew Rate | 1 Hz/s |
Phase Displacement Angle | 120° ± 1° (At 100% Balanced Load) & 120° ± 2° (At 100% Balanced Load) |
Transient Response & Response time | 0% to 90 % step load = +/- 5%, < 10 ms (Asynchronized Mode) |
Efficiency | 97.1% Dual Conversion Mode, 99.0% ECO Mode |
BATTERY | |
Battery Voltage | ± 240V DC Nominal (30 ~ 50 Nos. Configurable) |
SYSTEM FEATURE | |
Self-Diagnostics | During Power ON and Software Control |
EPO | UPS Shut down |
Transfer Time | Zero |
Alarm / Protections | Short Circuit, Input Under/Over Voltage, Over Temperature, Over Load, DC BUS Under / Over Voltage and Battery low |
Event Logging & Statistical Data | 16,384 events on LCD: Over temp, DC Bus Fail, Fan Fail, Fuse Fail, Overload, Short- circuit, Device Fail, Inverter Fail, Rectifier Fail, Bypass Fail, etc |
Display | Touch Screen LCD & LED Indication |
ENVIRONMENTAL | |
Temperature | Operating: 0~50°C*, Storage: -25ºC ~ 70ºC |
Humidity / Altitude | 0~95% RH Non-condensing / <1500 M (above sea level) without derating, Derating 1% for each additional 100m. |
Noise | <55dBA |
STANDARDS | |
Quality | ISO 9001, ISO 14001, ISO 27001, ISO 50001, RoHS |
Safety | IEC/EN62040-1 |
EMC / Performance | Complying to CE, IEC/EN62040-2; IEC/EN62040-3 |
COMMUNICATION INTERFACE | |
Standard | Rack: RS232, RS485, Dry Contact |
Optional | BMS/ RS485/ SNMP / ModBus / Dry Contact (Output Dry contact : 6 configurable for 21 events including Battery breaker shunt trip, back feed protection, EPO activated etc. & Input Dry contact : 4 / Parallel Port (LBS) / REPO / External Battery Temperature sensor / External switch Breaker status |
Monitoring Software | NetAgent Utility v5.8 / Muser 4000 / Power Manager |