| MODEL | MFII1106L16 | MFII1110L16 | |
| Capacity | 6 kVA | 10 kVA | |
| INPUT | |||
| Nominal Voltage | 220V / 230V / 240V AC (L+N+PE) | ||
| Operating Voltage Range | 110V~300V AC Load Dependent | ||
| Operating Frequency Range | 50 / 60 Hz ± 10% (Auto Sensing) | ||
| Power Factor | ≥0.99 | ||
| Bypass | Voltage | - 40% ~ +15% (Configurable) | |
| Frequency | ± 5% (Configurable) | ||
| ECO Range | Same as the Bypass, can be configured | ||
| Generator Input | Compatible | ||
| OUTPUT | |||
| Rated Voltage | 220V / 230V / 240V AC L+N+PE (Configurable) | ||
| Power Factor | 1.0 | ||
| Voltage Regulation | ±1% | ||
| Frequency | Auto Sensing 50 / 60 Hz ± 1~10% Sync Mode (Configurable), 50/60 Hz ± 0.5 Hz Battery Mode | ||
| Crest Factor | 3:1 | ||
| Overload | ≤105% for Continuos, ≤ 125% for 10 Min, ≤ 150% for 60 Sec, ≥ 150% for 200ms | ||
| Harmonic Distortion (THDv) | ≤ 1% | ||
| Efficiency | 94.0% Dual Conversion Mode, 99.0% ECO Mode | ||
| BATTERY | |||
| Battery Voltage | 192V DC / 216V & 240V DC (Configurable) | ||
| Typical Recharge Time | 4-5 Hours to 90% of full Capacity | ||
| Charge Current | 14A | ||
| SYSTEM FEATURES | |||
| IP Protection | IP20 | ||
| Transfer Time | Zero | ||
| EPO / ECO / CVCF | Shutdown UPS Immediately / ECO and CVCF Mode can be Configurable | ||
| Alarm / Protection | Short Circuit, Input Under/Over Voltage, Over Temperature, Over Current, Over Load, DC BUS Under / Over Voltage and Battery low | ||
| LED Display | Line Mode, Backup Mode, ECO Mode, Bypass Mode, Battery Low, Overload & UPS Fault | ||
| LCD Display | Input Voltage, Input Frequency, Output Voltage, Frequency, Current; Load Percentage, Battery Voltage, Charging/ Discharging/Current Temperature & Remaining Battery Backup Time, Load VA/W, Load and Battery Barograph | ||
| ENVIRONMENTAL | |||
| Temperature | Operating: 0~50°C*, Storage: -15ºC ~ 60ºC | ||
| Humidity / Altitude | 0~95% RH Non-condersing / <1500 M | ||
| Noise | <55dBA | ||
| PHYSICAL | |||
| Dimension WxDxH (mm) | 250 x 580 x 655 | ||
| Net Weight (Kg) | 33 | 36 | |
| STANDARDS | |||
| Quality | ISO 90001, ISO 14001, ISO 27001, ISO 45001, ISO 50001, BIS, RoHS, FCC | ||
| Safety | IEC/EN62040-1; Conformity to IEC / EN | ||
| EMC / Performance | IEC/EN62040-2; IEC/EN62040-3, Complying to CE, Compliance to UL | ||
| COMMUNICATION INTERFACE | |||
| Standard | RS-232 | ||
| Optional | SNMP / ModBus / Dry Contact / USB / RS-485 / SMS Alert Card | ||
| Monitoring Software | NetAgent Utility v5.8 / View Power / UPSilon 2000 / Muser 4000 | ||
For More Information about product please contact us