Technical Specifications of MSI Series 1~10KVA | ||||||||||||
STANDARD MODEL | MSI1101B2 | MSI1102B4 | MSI1103B6 | MSI1106B16 | MSI1110B16 | |||||||
LONG-RUN MODEL | MSI1101L3 | MSI1102L6 | MSI1103L6 | MSI1106L16 | MSI1110L16 | |||||||
PHASE | Single phase with ground | |||||||||||
CAPACITY * | 1000 VA / 900 W | 2000 VA / 1800 W | 3000 VA / 2700 W | 6000VA / 5400W | 10000 VA / 9000 W | |||||||
INPUT | ||||||||||||
Nominal Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC | 208/220/230/240VAC | ||||||||||
Input Voltage Range | 55-150 VAC or 110-300 VAC (Based on load at 50%) 85-140VAC or 160-280VAC (Based on load at 100%) | 110-300 VAC (Based on load at 50%) 176-300 VAC (Based on load at 100%) | ||||||||||
Frequency Range | 40 Hz ~ 70 Hz | 46~54 Hz or 56~64 Hz | ||||||||||
Power Factor | ≧ 0.99 @ Nominall Voltage (100% load) | |||||||||||
OUTPUT | ||||||||||||
Output Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC | 208/220/230/240VAC | ||||||||||
Voltage Regulation | ± 1 % | |||||||||||
Frequency Range (Synchronized Range) | 47~ 53 Hz or 57 ~ 63 Hz | 46~54 Hz or 56~64 Hz | ||||||||||
Frequency Range (Batt. Mode) | 50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz | 50 Hz or 60Hz ± 0.1 Hz | ||||||||||
Current Crest Ratio | 3:1 | |||||||||||
Harmonic Distortion | ≦ 3 % THD (Linear Load) ≦ 6 % THD (Non-linear Load) |
≦ 3 % THD (Linear Load) ≦ 5 % THD (Non-linear Load) |
||||||||||
Transfer Time | AC Mode to Battery Mode | Zero | ||||||||||
Inverter to Bypass | 4 ms (Typical) | Zero | ||||||||||
Waveform (Batt. Mode) | Pure Sinewave | |||||||||||
EFFICIENCY | ||||||||||||
AC Mode | 88% | 89% | 90% | 92% | 93% | |||||||
Battery Mode | 83% | 87% | 88% | 90% | 91% | |||||||
BATTERY | ||||||||||||
Standard Model | Battery Type | 12V/9Ah | 12V/9Ah | 12V/9Ah | 12V/9Ah | |||||||
Numbers | 2 | 4 | 6 | 16 | 16 | |||||||
Typical Recharge Time | 4 hours recover to 90% capacity | 9 hours recover to 90% capacity | ||||||||||
Charging Current (max.) | 1 A | 1 A / 2 A | ||||||||||
Charging Voltage | 27.4VDC ± 1% | 54.7 VDC ±1% | 82.1 VDC ±1% | 218.4 VDC±1% | 218.4 VDC±1% | |||||||
Long-run Model ** | Battery Type | Depending on the capacity of external batteries | ||||||||||
Numbers | 3 | 6 | 6 | 16 ~ 20 (Adjustable) | ||||||||
Charging Current (max.) | 1A/2A/4A/6A (Adjustable) | 1A/2A/4A/6A (Adjustable, 6A is only available for 16pcs batteries) | ||||||||||
Charging Voltage | 41.0VDC ± 1% | 82.1 VDC ±1% | 82.1 VDC ±1% | 273 VDC ±1% (Based on 20pcs batteries) | ||||||||
INDICATORS | ||||||||||||
LCD | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators | |||||||||||
ALARM | ||||||||||||
Battery Mode | Sounding every 4 seconds | |||||||||||
Low Battery | Sounding every second | |||||||||||
Overload | Sounding twice every second | |||||||||||
Fault | Continuously sounding | |||||||||||
PHYSICAL | ||||||||||||
Standard Model | Dimension, D x W x H (mm) | 282 x 145 x 220 | 397 x 145 x 220 | 421 x 190 x 318 | 369 x 190 x 688 | 442 x 190 x 688 | ||||||
Net Weight (kgs) | 9.8 | 17 | 27.6 | 61 | 66 | |||||||
Long-run Model ** | Dimension, D x W x H (mm) | 282 x 145 x 220 | 397 x 145 x 220 | 369 x 190 x 318 | 442 x 190 x 318 | |||||||
Net Weight (kgs) | 4.1 | 6.8 | 7.4 | 12 | 16 | |||||||
ENVIRONMENT | ||||||||||||
Humidity | 20-90 % RH @ 0- 40°C (Non-condensing) | 0-95% RH @ 0-50°C (non-condensing) |
0-95% RH @ 0-40°C (non-condensing) |
|||||||||
Noise Level | Less than 50dB @ 1 Meter | Less than 55dB @ 1 Meter | Less than 58dB @ 1 Meter | |||||||||
MANAGEMENT | ||||||||||||
Smart RS-232 / USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC | |||||||||||
Optional SNMP | Power management from SNMP manager and web browser | |||||||||||
*1-3KVA: Derate to 80% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 100/200/208VAC. 6-10KVA: Derate to 60% of capacity in Frequency converter mode and to 90% when the output voltage is adjusted to 208VAC. **Long-run model is only available for 200/208/220/230/240VAC systems (200VAC system only available for 1-3KVA). Product specifications are subject to change without further notice. |
||||||||||||
Technical Specifications of Battery Pack | ||||||||||||
MODEL BPMSI01K6N9 BPMSI0203K12N9 BPMSI0203K18N9 | ||||||||||||
Supported UPS | 1K | 3K | 3K | |||||||||
Battery Type | 12 V/9 Ah | 12 V/9 Ah | 12 V/9 Ah | |||||||||
Battery Number | 6 pcs | 12 pcs | 18 pcs | |||||||||
Battery Voltage | 24VDC | 72 VDC | 72 VDC | |||||||||
Dimension(DxWxH) | 397 X 145 X 220 | 421 X 190 X 318 | 535 X 190 X 318 | |||||||||
Net Weight (kgs) | 20 | 40 | 67.5 | |||||||||
MODEL BPMSI0610K16N9 BPMSI0610K32N9 BPMSI0610K40N9 | ||||||||||||
Supported UPS | 6K | 6K | 10K | |||||||||
Battery Type | 12 V/9 Ah | 12 V/9 Ah | 12 V/9 Ah | |||||||||
Battery Number | 16 pcs | 32 pcs | 40 pcs | |||||||||
Battery Voltage | 192VDC | 192VDC | 240 VDC | |||||||||
Dimension(DxWxH) | 442 x 190 x 318 | 442 x 190 x 688 | 442 x 190 x 688 |
|
||||||||