Features:
MODEL | MFII3110L16 | MFII3115L16 | MFII3120L16 | MFII3130L16 | ||
Capacity | 10 kVA | 15 kVA | 20 kVA | 30 kVA | ||
INPUT | ||||||
Nominal Voltage | 380V / 400V / 415V AC (3P+N+PE) | |||||
Operating Voltage Range | 208V~480V AC Load Dependant | |||||
Operating Frequency Range | 50 / 60 Hz ± 10% (Auto Sensing) | |||||
Power Factor | ≥0.99 | |||||
Bypass | Voltage | - 40% ~ +15% (Configurable) | ||||
Frequency | ± 5% (Configurable) | |||||
ECO Range | Same as the Bypass, can be configured | |||||
Generator Input | Compatible | |||||
OUTPUT | ||||||
Rated Voltage | 220V / 230V / 240V AC L+N+PE (Configurable) | |||||
Power Factor | 1.0 | |||||
Voltage Regulation | ±1% | |||||
Frequency | Auto Sensing 50 / 60 Hz ± 1~10% Sync Mode (Configurable), 50/60 Hz ± 0.5 Hz Battery Mode | |||||
Crest Factor | 3:1 | |||||
Overload | ≤105% for Continuos, ≤ 125% for 10 Min, ≤ 150% for 60 Sec, ≥ 150% for 200ms | |||||
Harmonic Distortion (THDv) | ≤ 1% | |||||
Efficiency | 94.0% Dual Conversion Mode, 99.0% ECO Mode | |||||
BATTERY | ||||||
Battery Voltage | 192V DC / 216V & 240V DC (Configurable) | |||||
Typical Recharge Time | 4-5 Hours to 90% of full Capacity | |||||
Charge Current | 14A | 16A | 18A | 20A | ||
SYSTEM FEATURES | ||||||
IP Protection | IP20 | |||||
Transfer Time | Zero | |||||
EPO / ECO / CVCF | Shutdown UPS Immediately / ECO and CVCF Mode can be Configurable | |||||
Alarm / Protection | Short Circuit, Input Under/Over Voltage, Over Temperature, Over Current, Over Load, DC BUS Under / Over Voltage and Battery low | |||||
LED Display | Line Mode, Backup Mode, ECO Mode, Bypass Mode, Battery Low, Overload & UPS Fault | |||||
LCD Display | Input Voltage, Input Frequency, Output Voltage, Frequency, Current; Load Percentage, Battery Voltage, Charging/ Discharging/Current Temperature & Remaining Battery Backup Time, Load VA/W, Load and Battery Barograph | |||||
ENVIRONMENTAL | ||||||
Temperature | Operating: 0~50°C*, Storage: -15ºC ~ 60ºC | |||||
Humidity / Altitude | 0~95% RH Non-condersing / <1500 M | |||||
Noise | <55dBA | <58dBA | ||||
PHYSICAL | ||||||
Dimension WxDxH (mm) | 250 x 580 x 655 | |||||
Net Weight (Kg) | 33 | 37 | 38 | 41 | ||
STANDARDS | ||||||
Quality | ISO 90001, ISO 14001, ISO 27001, ISO 45001, ISO 50001, BIS, RoHS, FCC | |||||
Safety | IEC/EN62040-1; Conformity to IEC / EN | |||||
EMC / Performance | IEC/EN62040-2; IEC/EN62040-3, Complying to CE, Compliance to UL | |||||
COMMUNICATION INTERFACE | ||||||
Standard | RS-232 | |||||
Optional | SNMP / ModBus / Dry Contact / USB / RS-485 | |||||
Monitoring Software | NetAgent Utility v5.8 / View Power / UPSilon 2000 / Muser 4000 |
For More Information about product please contact us