MODEL | EPX+33160L32 | EPX+33200L32 | EPX+33400L32 | EPX+33500L32 |
Capacity | 160kVA | 200kVA | 400kVA | 500kVA |
INPUT | ||||
Rated AC Voltage | 380V / 400V / 415V AC (3Ph+N+PE) | |||
Voltage Range | 290V ~ 480V AC ± 5V | |||
Frequency Range | 50 / 60 Hz ± 10% Auto Sensing | |||
Power Factor | ≥ 0.95 (With Filter) | |||
Walk-in Time | 5 ~ 300 Sec. (Configurable) | |||
BYPASS | ||||
Rated Voltage | 380V / 400V / 415V AC (3Ph+N+PE) | |||
Voltage Range | + 20%, -30% (Configurable) | |||
Frequency Range | 50 / 60 Hz ± 10% (Configurable) | |||
BATTERY | ||||
Battery Voltage | 384V DC Standard (360 ~ 408 Configurable) | |||
Ripple | ≤ 1% | |||
Charging Current Max. (A) | 0.10C to 0.25C upto 100~300Ah at 100% Load (Configurable) | |||
OUTPUT | ||||
Rated Voltage | 380V / 400V / 415V AC (3Ph+N) | |||
Frequency Range | Auto Sensing 50 / 60 Hz ± 1~10% Sync Mode (Configurable), 50/60 Hz ± 0.1 Hz Battery Mode | |||
Voltage Regulation | ±1% | |||
Harmonic Distortion (THDv) | ≤ 1% Linear Load, ≤ 5% Non-Linear Load | |||
Crest Factor / Transfer Time | 3:1 / Zero | |||
Efficiency | Up to 93.0% Dual Conversion Mode, 99.0% ECO Mode | |||
Overload | ≤ 110% for 60 Min, ≤ 125% for 10 Min, ≤ 150% for 1 Min, ≥ 150% for 300 ms | |||
SYSTEM FEATURES | ||||
Parallel | Up to 6 Units (Optional) | |||
Display | 7" Touch Screen LCD with LED Mimic diagram | |||
IP Rating | IP20 | |||
Alarm / Protection | Short Circuit, Input Under/Over Voltage, Over Temperature, Over Current, | |||
Audible Alarms | Alarm for battery Low, DC High, Inverter Under/Over Voltage, Overload, Short Circuit, Fan Failure & UPS Fault | |||
LED Indicatios | Bypass, Mains, Battery and Fault | |||
LCD Information | Input Voltage & Freq.; Output Voltage, Current, kVA, kW, Total Power, PF, Load % Per Phase, Load % Total & Freq.; Bypass Voltage & Freq.; Inverter Voltage & Freq.; Battery Voltage, DC Bus Voltage, Charging Current, Discharging Current, Temperature. | |||
ENVIRONMENTAL | ||||
Temperature | Operating: 0~50°C*, Storage: -10ºC ~ 55ºC | |||
Humidity / Altitude | 0~95% RH Non-condensing / <1500 M | |||
Noise | Low Audible Noise Level | |||
STANDARDS | ||||
Quality | ISO 9001, ISO 14001, ISO 27001, ISO45001, ISO 50001, RoHS | |||
Safety | IEC/EN62040-1 | |||
EMC / Performance | IEC/EN62040-2; IEC/EN62040-3, Complying to CE | |||
PHYSICAL | ||||
Dimensions WxDxH (mm) | 890x790x1600 | 1200x800x1600 | 1400x1000x1900 | 2800x1040x1900 |
Weight (Kg) | 740 | 1030 | 1640 | 3510 |
COMMUNICATION INTERFACE | ||||
Standard | RS-232 | |||
Optional | SNMP / ModBus / Dry Contact / USB / RS-485 | |||
Monitoring Software | NetAgent / Muser4000 |