True Online Double Conversion Topology
Output Isolation Transformer
Wide Input Voltage Range
User Friendly Digital LC Display
Rear Panel
MODEL | CP3305L16 | CP3310L20 | CP3315L20 | CP3320L20 | CP3320L30 |
Capacity | 5 kVA | 10 kVA | 15 kVA | 20 kVA | 20 kVA |
INPUT | |||||
Voltage Range | 320V ~ 480V AC, Three Phase (4 Wire) | ||||
Frequency Range (Hz) | 50 / 60 Hz ±10% | ||||
Power Factor | >0.95 | ||||
OUTPUT | |||||
Power Factor | 0.8 (Standard) 0.9 (Optional) | ||||
Voltage (V) | 400V AC | ||||
Frequency (Hz) | 50Hz ± 0.1% | ||||
Waveform | Pure Sine Wave | ||||
Efficiency | 94.0% | ||||
THDv | ≤1% | ||||
Overload | ≤110% for 60 Min, ≤125% for 10 Min, ≤150% for 1 Min and ≥ 150% for 300 ms | ||||
Isolation Transformer | Inbuilt Isolation Transformer | ||||
BATTERY | |||||
Battery Voltage | 192V | 240V | 360V | ||
Charging Current (Max) | 1A ~ 10A Standard (High Rating Optional) | ||||
Charging Time | 4-5 Hrs. for 95% | ||||
SYSTEM FEATURES | |||||
Display | LCD | Input and Output Voltage, Input and Output Frequency, Load & Battery % | |||
LED | Mains, AC Mode, DC Mode, Low Battery, Overload | ||||
Alarm | Battery Low Voltage, Abnormal Power Supply, UPS Failure, Overload | ||||
Protection | Short Circuit, Input Under/Over Voltage, Over Temperature, Over Current, Over Load, DC BUS Under / Over Voltage and Battery low | ||||
ENVIRONMENTAL | |||||
Temperature | Operating: 0~50°C*, Storage: -15ºC ~ 60ºC | ||||
Humidity / Altitude | 0~95% RH Non-condensing / <1500 M | ||||
Noise | <50dBA | ||||
STANDARDS | |||||
Quality | ISO 9001, ISO 14001, ISO 27001, ISO 45001, ISO 50001, RoHS | ||||
Safety | IEC/EN62040-1 | ||||
EMC / Protection | IEC/EN62040-2; IEC/EN62040-3, Complying to CE | ||||
PHYSICAL | |||||
Dimension WxDxH (mm) | 280x615x685 | ||||
Weight (Kg) | 160 | 170 | 180 | 185 | 225 |
COMMUNICATION INTERFACE | |||||
Optional | SNMP / ModBus / Dry Contact / USB / RS-485 / RS-232 | ||||
Monitoring Software | NetAgent / UPSilon 2000 |