MODEL GTM3330L32 | GTM3360L32 | GTM3390L32 | |||
Capacity (kVA) | 30 | 60 | 90 | ||
INPUT | |||||
Nominal Voltage | 380V / 400V / 415V AC (3Ph+N+PE) | ||||
Voltage Range | +25% – 35% | ||||
Frequency Range | 50 / 60 Hz ± 20% Auto Sensing | ||||
Power Factor | ≥ 0.99 | ||||
Harmonic Distortion (THDi) | ≤3% | ||||
Bypass Range | Voltage | 35% (Optional -20%, -30%) | |||
Frequency | ± 10% (Configurable) | ||||
Generator Input | Support | ||||
OUTPUT | |||||
Output Voltage | 380V / 400V / 415V AC (3Ph+N+PE) | ||||
Voltage Regulation | ± 1% | ||||
Power Factor | 0.9 Standard / Unity Optional | ||||
Frequency | Auto Sensing 50 / 60 Hz ± 1~10% Sync Mode (Configurable), 50/60 Hz ± 0.1 Hz Battery Mode | ||||
Crest Factor | 3:1 | ||||
Harmonic Distortion (THDv) | ≤ 1% | ||||
Overload | ≤ 125% for 10 Min, ≤150% for 1 Min, ≥ 150% for 200 ms | ||||
Efficiency | 95.5% Dual Conversion Mode, 99.0% ECO Mode | ||||
BATTERY | |||||
Battery Voltage | Standard Unit: ± 216V DC; Unit configurable Voltage: ± 192V / ± 204V / ± 216V / ± 228V / ± 240V DC | ||||
SYSTEM FEATURES | |||||
Transfer Time | Zero | ||||
Self-Diagnostics / EPO | Upon Power On and Software Control / Inbuilt | ||||
IP Protection | IP 20 | ||||
Alarm / Protection | Line Failure, Battery Low, Overload, System Fault and Short Circuit | ||||
Display | LED | Line Mode, Bypass Mode, Battery Low, Overload and UPS Fault Codes | |||
LCD | Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load %, Battery Voltage & Temperature, Output W/VA | ||||
Parallel | Inbuilt | ||||
ENVIRONMENT | |||||
Temperature | Operating: 0~50°C*, Storage: -15ºC ~ 60ºC | ||||
Humidity / Altitude | 0~95% RH Non-condensing / <1500 M | ||||
Noise | ≤ 65dBA | ||||
STANDARDS | |||||
Quality | ISO 9001, ISO 14001, ISO 27001, ISO 45001, ISO 50001, RoHS | ||||
Safety | IEC/EN62040-1 | ||||
EMC / Performance | IEC/EN62040-2; IEC/EN62040-3, Complying to CE | ||||
PHYSICAL | |||||
Dimension WxDxH (mm) | 600x780x1200 | ||||
Net Weight (Kg) | 158 | 190 | 196 | ||
COMMUNICATION INTERFACE | |||||
Standard | RS-232 | ||||
Optional | SNMP / ModBus / Dry Contact / USB / RS-485 | ||||
Monitoring Software | NetAgent Utility v5.8 / View Power / UPSilon 2000 / Muser 4000 |