MODEL | MFII1106L16 | MFII1110L16 | MFII1111L16-E6 | |
Capacity | 6 kVA | 10 kVA | 11 kVA | |
INPUT | ||||
Nominal Voltage | 220V / 230V / 240V AC (L+N+PE) | |||
Operating Voltage Range | 110V~300V AC Load Dependent | |||
Operating Frequency Range | 50 / 60 Hz ± 10% (Auto Sensing) | |||
Power Factor | ≥0.99 | |||
Bypass | Voltage | - 40% ~ +15% (Configurable) | ||
Frequency | ± 5% (Configurable) | |||
ECO Range | Same as the Bypass, can be configured | |||
Generator Input | Compatible | |||
OUTPUT | ||||
Rated Voltage | 220V / 230V / 240V AC L+N+PE (Configurable) | |||
Power Factor | 1.0 | |||
Voltage Regulation | ±1% | |||
Frequency | Auto Sensing 50 / 60 Hz ± 1~10% Sync Mode (Configurable), 50/60 Hz ± 0.5 Hz Battery Mode | |||
Crest Factor | 3:1 | |||
Overload | ≤105% for Continuos, ≤ 125% for 10 Min, ≤ 150% for 60 Sec, ≥ 150% for 200ms | |||
Harmonic Distortion (THDv) | ≤ 1% | |||
Efficiency | 94.0% Dual Conversion Mode, 99.0% ECO Mode | |||
BATTERY | ||||
Battery Voltage | 192V DC / 216V & 240V DC (Configurable) | |||
Typical Recharge Time | 4-5 Hours to 90% of full Capacity | |||
Charge Current | 14A | |||
SYSTEM FEATURES | ||||
IP Protection | IP20 | |||
Transfer Time | Zero | |||
EPO / ECO / CVCF | Shutdown UPS Immediately / ECO and CVCF Mode can be Configurable | |||
Alarm / Protection | Short Circuit, Input Under/Over Voltage, Over Temperature, Over Current, Over Load, DC BUS Under / Over Voltage and Battery low | |||
LED Display | Line Mode, Backup Mode, ECO Mode, Bypass Mode, Battery Low, Overload & UPS Fault | |||
LCD Display | Input Voltage, Input Frequency, Output Voltage, Frequency, Current; Load Percentage, Battery Voltage, Charging/ Discharging/Current Temperature & Remaining Battery Backup Time, Load VA/W, Load and Battery Barograph | |||
ENVIRONMENTAL | ||||
Temperature | Operating: 0~50°C*, Storage: -15ºC ~ 60ºC | |||
Humidity / Altitude | 0~95% RH Non-condersing / <1500 M | |||
Noise | <55dBA | |||
PHYSICAL | ||||
Dimension WxDxH (mm) | 250 x 580 x 655 | |||
Net Weight (Kg) | 33 | 36 | ||
STANDARDS | ||||
Quality | ISO 90001, ISO 14001, ISO 27001, ISO 45001, ISO 50001, BIS, RoHS, FCC | |||
Safety | IEC/EN62040-1; Conformity to IEC / EN | |||
EMC / Performance | IEC/EN62040-2; IEC/EN62040-3, Complying to CE, Compliance to UL | |||
COMMUNICATION INTERFACE | ||||
Standard | RS-232 | |||
Optional | SNMP / ModBus / Dry Contact / USB / RS-485 / SMS Alert Card | |||
Monitoring Software | NetAgent Utility v5.8 / View Power / UPSilon 2000 / Muser 4000 |