MODEL | UPSX1101 | UPSX1103L4 | UPSX1103L8 |
Capacity | 2kVA | 3kVA | |
INPUT | |||
Voltage (VAC) | 100~300V AC (1Ph+N+PE) Load Dependent | ||
Frequency (Hz) | 45~65 (Auto Sensing) | ||
OUTPUT | |||
Voltage | 230±10% (1Ph+N+PE) | ||
Frequency on Battery | 50±1Hz | ||
Waveform | Sine Wave | ||
Transfer time (ms) | 4-8 ms Typical | ||
Load PF | 0.6 (Standard), 0.7, 0.8 (Optional) | ||
BATTERY | |||
Type | Sealed Maintenance Free Lead Acid VRLA | ||
Battery Voltage | 12V / 24V / 36V / 48V / 72V / 96V as per customer requirement | ||
Charge Current | 10A ±1A (Adjustable) | ||
Recharging Time | 6-8 Hrs. to 90% After Complete Discharge | ||
SYSTEM FEATURES | |||
Audible | Low Battery, Overload, Fault conditions and Battery Mode | ||
Display | LED Indicator for AC Mode : Green Lighting, Battery Backup Mode : Orange Lighting, Fault Mode : Red Lighting |
LCD + LED | |
Battery Charging Mode: When Battery is not Full Charge in Line Mode, White LED Flashing every 2 Sec., When Battery Full, White LED lighting | |||
Overload: Red Flashing Every 0.5 Sec. | |||
Protection | Battery Low, Overload, Short Circuit, AC Input Low/ High & Fault conditions | ||
Cold Start | Yes | ||
PHYSICAL | |||
Dimension WxDxH (mm) | 220x350x340 | 195x455x330 | |
Net Weight (Kg) | 25 | 33 | |
Backup Outlet | 1 Universal Socket 15A | ||
STANDARD | |||
Quality | ISO 9001, ISO 14001, ISO 45001, ISO 27001, BIS and RoHS | ||
Safety | IEC/EN62040-1 | ||
EMC / Performance | IEC/EN62040-2, IEC/EN62040-3, Complying to CE | ||
ENVIRONMENTAL | |||
Temperature | Operating: 0~50°C*, Storage: -10ºC ~ 55ºC | ||
Humidity / Altitude | 0~95% RH Non-condensing / <1500 M | ||
Noise | Low Audible Noise Level | ||
COMMUNICATIONS | |||
Communication Port | RS-232 / USB (Optional) | ||
Monitoring Software | View Power/ UPSilon 2000 (Optional) |