The PS50 Series is a modular, true online double conversion UPS (50kVA–1000kVA) designed for critical loads in medium to large data centers. It features advanced 3-level IGBT and PFC input control with phase sequence correction, delivering up to 97.1% efficiency. With compact design, up to 1000kVA fits in one cabinet, and scalability up to 6000kVA with parallel units ensures high availability and flexibility.
| Model | PS50R4MU36 | PS50R6MU42 | PS50R10MU42 | PS50R16MU42 | PS50R20MU42 | |
|---|---|---|---|---|---|---|
| Rating (kVA) Configurable | 200 | 300 | 600 | 800 | 1000 | |
| Dimension WxDxH (mm) | 600x850x1600 | 600x850x2000 | 1200x850x2000 | 2000x850x2000 | ||
| Weight (Kg) | 230 | 260 | 650 | 980 | 1050 | |
| Feature | Hot-Swappable Inbuilt Static Bypass Module for Max. Inbuilt Maintenance Bypass Switch | |||||
| Bypass | Voltage | Max. Voltage: ± 15% (Optional ± 5%, ± 10%, ± 25%) | ||||
| Frequency | 50 / 60 Hz Auto Sensing ± 1 Hz, ± 5 Hz | |||||
| Overload | 135% Overload for 1 Min. ; >1000% Overload for 100 ms | |||||
| Monitoring | 7 Inch. Touch Screen Display+Keyboard | |||||
| Nos. of Module | 50kVA x 04 | 50kVA x 06 | 50kVA x 12 | 50kVA x 16 | 50kVA x 20 | |
| SPECIFICATION OF MODULE | ||||||
| MODULE 50kVA | PS50M3350 | |||||
| Dimension WxDxH (mm) | 440x620x130 (3U) | |||||
| Weight (Kg) Each 50kVA | 34 Kg | |||||
| INPUT | ||||||
| Nominal Voltage | 380V / 400V / 415V AC (3P+N+PE) | |||||
| Operating Voltage Range | 228V - 480V AC Load Dependent | |||||
| Operating Frequency Range | 40Hz - 70Hz Auto Sensing | |||||
| Power Factor | ≥ 0.99 | |||||
| Harmonic Distortion (THDi) | ≤ 3% | |||||
| Generator Input / Walking | Support / 0-40 Sec. (Configurable) | |||||
| OUTPUT | ||||||
| Output Voltage | 380V / 400V / 415V AC (3P+N+PE) | |||||
| Voltage Regulation | ± 1% | |||||
| Power Factor | 1.0 (Unity) | |||||
| Frequency | Auto Sensing 50 / 60 Hz ± 3Hz Sync Mode (Configurable), 50/60 Hz ± 0.1 Hz Battery Mode | |||||
| Crest Factor | 3:1 | |||||
| Harmonic Distortion (THDv) | ≤ 1% | |||||
| Over Load | ≤ 125% for 10 min, ≤ 150% for 1 min, > 150% for 200 ms | |||||
| Efficiency | 97.1% Dual Conversion 99.0% ECO Mode | |||||
| BATTERY | ||||||
| Battery Voltage | ± 240V DC Nominal (30 – 50 Nos. Configurable) | |||||
| SYSTEM FEATURE | ||||||
| Self-Diagnostics | During Power On and Software Control | |||||
| EPO | UPS Shut Down | |||||
| Transfer Time | Zero | |||||
| Alarm / Protections | Short Circuit, Input Under/Over Voltage, Over Temperature, Over Load, DC BUS Under / Over Voltage and Battery low |
|||||
| Display | Touch Screen LCD & LED Indication | |||||
| ENVIRONMENTAL | ||||||
| Temperature | Operating: 0-50°C; Storage: -15°C - 70°C | |||||
| Humidity / Altitude | 0-95% RH Non-condensing / <1500 M (Above sea level) without de-rating, Derating 1% for each additional 100m. | |||||
| Noise | <65dBA | |||||
| STANDARDS | ||||||
| Quality | ISO 9001, ISO 14001, ISO 27001, ISO 50001, RoHS | |||||
| Safety | IEC/EN62040-1 | |||||
| EMC / Performance | Complying to CE, IEC/EN62040-2, IEC/EN62040-3 | |||||
| COMMUNICATION INTERFACE | ||||||
| Standard | Rack:RS232, RS485, Dry Contact | |||||
| Optional | BMS/ RS485/ LBS / SNMP / ModBus / Dry Contact / Parallel, Dry contact, Relay Card, Battery temperature sensor | |||||
| Monitoring Software | NetAgent Utility v5.8 / Muser 4000 / Power Manager | |||||
For More Information about product please contact us