PS 100 Series

The PS100 series modular, true online double conversion transformer-less design with 3-Level IGBT Inverter topology UPS ranging from 100kVA to 1200kVA is designed to protect any critical load for medium and large data center achieving maximum availability. The PS100 series feature the latest technology of DSP Microprocessor based control, using IGBT devices, high switching frequency PWM and PFC input control & Input Phase Sequence Correction, which guarantees ultra high efficiency of 97.1% and reliability.

Submit Your Enquiry & Our Experts Will Assist You

Thank you! Your submission has been received!
Oops! Something went wrong while submitting the form.
Features:
  • Compact 1000kVA UPS in 1m² footprint.
  • 100kVA hot-swappable power modules (3U height).
  • Ultra-efficient 97.1% with 3-level IGBT technology.
  • Intelligent battery management extends battery life.
  • Scalable from 100kVA to 1200kVA per cabinet.
  • Expandable up to 7200kVA with 6 units parallel.
  • Compatible with lithium batteries.
  • 7” multilingual touchscreen with waveform recording.
  • Smart sleep mode saves energy under low load.
  • Self-loading feature for internal load testing.
  • Supports 100% unbalanced load operation.
  • Multi-protocol communication: RS232, RS485, USB, SNMP, AS400.
  • Built-in EHS mode enables input power factor correction and harmonic filtration, delivering up to 98.6% operating efficiency.

SPECIFICATION OF RACK
MODEL PS100R4MU42 PS100R5MU42 PS100R6MU42 PS100R8MU42 PS100R10MU42 PS100R12MU42
Rating (kVA) Configurable 400 500 600 800 1000 1200
Dimension WxDxH (mm) 800 x 1000 x 2000 800 x 1000 x 2000 (S)
1400 x 1000 x 2000 (F)
1400 x 1000 x 2000 (S)
1800 x 1000 x 2000 (F)
Weight (Kg) 305 (S)
350 (F)
330 (S)
380 (F)
350 (S)
410 (F)
405 (S)
780 (F)
690 (S)
850 (F)
760 (S)
920 (F)
Bypass Feature Hot-Swappable Inbuilt Static Bypass Module for Max. Inbuilt Maintenance Bypass Switch
Voltage Max. Voltage: + 15% (Optional +5%, +10%, +20%), Min. Voltage: -45% (Optional -10%, -15%, -20% & -30%)
Frequency 50 / 60 Hz Auto Sensing ± 1Hz, ± 3Hz, ± 5Hz
Overload 135% Overload Continuous ; >1000% Overload for 100 ms
Monitoring 7 Inch. Touch Screen Display
Nos. of Module 100kVA x 04 100kVA x 05 100kVA x 06 100kVA x 08 100kVA x 10 100kVA x 12
Switches & Connections Connections - Rectifier Input / Output / Bypass Input / Battery & Switches - Input, Bypass, Output & Maintenance Bypass
SPECIFICATION OF MODULE
MODULE PS100M33100
Dimension WxDxH (mm) 440 x 755 x 130 (3U)
Weight (Kg) Each 100kVA 52.5 Kg
INPUT
Nominal Voltage 380V / 400V / 415V AC (3Ph+N+PE)
Operating Voltage Range 138V - 322V AC for 40% Load & 323V - 485V AC for 100% Load
Operating Frequency Range 40Hz - 70Hz Auto Sensing
Power Factor ≥ 0.99
Harmonic Distortion (THDi) ≤ 3%
Generator Input / Walking Support / 0-40 Sec. (Configurable)
OUTPUT
Output Voltage 380V / 400V / 415V AC (3Ph+N+PE)
Voltage Regulation ± 1%
Power Factor 1.0 (Unity)
Frequency Auto Sensing 50 / 60 Hz ± 3Hz Sync Mode (Configurable), 50/60 Hz ± 0.1 Hz (Free Running / Self Clocked Mode)
Crest Factor 3:1
Harmonic Distortion (THDv) ≤ 1%
Over Load ≤110% for 60 min, ≤125 % for 10 min, ≤ 150% for 1 min, >150% for 200 ms
Slew Rate 1 Hz/s
Phase Displacement Angle 120° ± 1° (At 100% Balanced Load) & 120° ± 2° (At 100% Balanced Load)
Transient Response & Response time 0% to 90 % step load = +/- 5%, < 10 ms (Asynchronized Mode)
Efficiency 97.1% Dual Conversion Mode, 99.0% ECO Mode
BATTERY
Battery Voltage ± 240V DC Nominal (30 - 50 Nos. Configurable)
SYSTEM FEATURE
Self-Diagnostics During Power ON and Software Control
EPO UPS Shut down
Transfer Time Zero
Alarm / Protections Short Circuit, Input Under/Over Voltage, Over Temperature, Over Load, DC BUS Under / Over Voltage and Battery low
Event Logging & Statistical Data 16,384 events on LCD: Over temp, DC Bus Fail, Fan Fail, Fuse Fail, Overload, Short- circuit, Device Fail, Inverter Fail, Rectifier Fail, Bypass Fail, etc
Display Touch Screen LCD & LED Indication
ENVIRONMENTAL
Temperature Operating: 0~50°C*, Storage: -25°C ~ 70°C
Humidity / Altitude 0~95% RH Non-condensing / <1500 M (above sea level) without derating, Derating 1% for each additional 100m.
Noise <55dBA
STANDARDS
Quality ISO 9001, ISO 14001, ISO 27001, ISO 50001, RoHS
Safety IEC/EN62040-1
EMC / Performance Complying to CE, IEC/EN62040-2; IEC/EN62040-3
COMMUNICATION INTERFACE
Standard Rack RS232, RS485, Dry Contact
Optional BMS/ RS485/ SNMP / ModBus / Dry Contact (Output Dry contact : 6 configurable for 21 events including Battery breaker shunt trip, back feed protection, EPO activated etc. & Input Dry contact : 4 / Parallel Port (LBS) / REPO / External Battery Temperature sensor / External switch Breaker status
Monitoring Software NetAgent Utility v5.8 / Muser 4000 / Power Manager