PS 15 Series

Advance Fully Microprocessor DSP Based True Online double conversion, 3-Level IGBT Based Rectifier & Inverter Technology, Wide input voltage range, Wide input frequency range : 40-70Hz, Input current Harmonics : <3%, High input power factor : ≥ 0.99

Submit Your Enquiry & Our Experts Will Assist You

Thank you! Your submission has been received!
Oops! Something went wrong while submitting the form.
Features:
  • Advance Fully Microprocessor DSP Based True Online double conversion
  • 3-Level IGBT Based Rectifier & Inverter Technology
  • Wide input voltage range
  • Wide input frequency range : 40-70Hz
  • Input current Harmonics : <3%
  • High input power factor : ≥ 0.99
  • Rack Optimization battery group : 16/18/20 Nos.
  • High output power factor : 1.0 (kVA=kW)
  • 1-Phase & 3-Phase Input Configuration (Rack & Module Dependant)
  • Emergency power off function (EPO)
  • Generator compatible
  • Cold start function
  • Intelligent fan adjustment to extend fan life
  • Each module with individual display
  • Hot-Swappable Power Modules for Easy Maintenance
  • Built-in Active Power Factor Correction

RACK MODEL PS15R3MU PS15R5MU
Maximum Number of Modules 3 5
Maximum Capacity Capacity = No. of Modules x kVA of Module, Maximum Capacity = 50kVA
Dimension (WxDxH) in mm 600 x 840 x 1000 600 x 840 x 1400
Weight of Rack (kg) 142 156
POWER MODULE MODEL PS3105L16 PS3108L16 PS3110L16 PS3112L20 PS3115L20
Module Capacity (kVA) 5 8 10 12 15
INPUT
Nominal Voltage 380V / 400V / 415V AC (3Ph+N+PE)
Voltage Range 208V~480V AC Load Dependent
Frequency Range 40-70Hz
Power Factor ≥ 0.99
THDi ≤ 3%
Bypass Voltage Range Max. Voltage : 25% for 220/380V, 20% for 230/400V & 15% for 240/415V
Min. Voltage : -45% (Optional -10%, -20% & -30%)
OUTPUT
Output Voltage, Regulation 220V / 230V / 240V AC (L+N) ± 1%
Power Factor 1.0
Frequency Range Auto Sensing 50 / 60 Hz ± 1~10% Mains Synchronized (Configurable), 50 / 60 Hz ±0.1Hz Battery Mode
Crest Factor 3:1 (max.)
Harmonic Distortion ≤ 2 %
Transfer Time Zero
Waveform Pure Sinewave
Overload ≤ 110% for 60 min, ≤125% for 10 min, 150% for 200 ms
Efficiency 96.5% Dual Conversion Mode, 99% ECO Mode
Waveform Pure Sine Wave
BATTERY CHARGER
Battery Quantity 16~20 Nos.
Charging Current (Module) 16A
Rack with UPS
IP Protection IP 20
Alarm / Protection Short Circuit, Input Under/Over Voltage, Over Temperature, Over Current,
Over Load, DC Bus Under/Over Voltage and Battery Low
LED / LCD UPS status, Load % / VA / W, Battery level, Input/Output voltage, Discharge timer, and Fault Code
Display 7 inch LCD Display on rack
STANDARDS
Quality ISO 9001, ISO 14001, ISO 27001, ISO 45001, ISO 50001, RoHS
Safety IEC/EN62040-1
EMC / Performance IEC/EN62040-2; IEC/EN62040-3, Complying to CE
PHYSICAL
Dimension
W x D x H (mm) UPS Module
443 x 580 x 131 (3U)
Net Weight (kg)   UPS Module 29
ENVIRONMENT
Temperature Operating: 0 ~ 50°C*, Storage: -15 ~ 60°C
Humidity / Altitude 0-95% RH Non-condensing / <1500 m
Noise < 60dBA
COMMUNICATION
Standard RS-232, Battery Temp. Comm., RS-485, Parallel Intelligent slot x 2, Dry Contact
Optional SNMP / ModBus / USB
Monitoring Software NetAgent Utility v5.8 / View Power / UPSilon 2000 / Muser 4000