PS 12 Series

A modular UPS system with hot-swappable power modules (4kVA to 12kVA) and customizable 4-slot design. Features adjustable battery capacity, DSP technology for reliability, high input power factor , and supports 50/60Hz frequency conversion. Offers energy-saving ECO mode, emergency power off, generator compatibility, and high efficiency (up to 99.0%). Equipped with LCD displays for easy monitoring.

Submit Your Enquiry & Our Experts Will Assist You

Thank you! Your submission has been received!
Oops! Something went wrong while submitting the form.
Features:
  • Modular UPS with hot-swappable power modules (4kVA–12kVA)
  • Customizable 4-slot system with adjustable battery capacity  (32~40 Nos. of 12V Battery)
  • DSP technology for high reliability and 0.99 input power factor
  • Supports 50/60Hz frequency conversion and ECO mode for energy saving
  • Emergency Power Off (EPO) and generator compatible
  • High efficiency up to 96.8%, ECO mode up to 99.0%
  • LCD displays on cabinet (7”) and modules (4”) for easy monitoring

SPECIFICATION OF RACK
MODEL PS12R314MU17
PHASE 1 Phase In / 1 Phase Out 3 Phase In / 1 Phase Out 3 Phase In / 3 Phase Out
Rating (kVA) Maximum 48 48 48
Max. Power Module No. 4 Module
Dimension WxDxH (mm) 858x443x840 (WxDxH mm)
Weight (Kg) 71.5 Kgs
LC Display 7inch
SPECIFICATION OF MODULE
MODEL PS121104 PS121106 PS121110 PS1112 PS123104 PS123106 PS123110 PS123112 PS123304 PS123306 PS123310 PS123312
PHASE 1 Phase In / 1 Phase Out 3 Phase In / 1 Phase Out 3 Phase In / 3 Phase Out
CAPACITY (kVA) 04 06 10 12 04 06 10 12 04 06 10 12
PARALLEL CAPABILITY Yes, 4 Module
INPUT
Nominal Voltage 220V / 230V / 240V AC (1Ph+N+PE) 380V / 400V / 415V AC (3Ph+N+PE)
Voltage Range 110V~300V AC Load Dependent 190V~520V AC Load Dependent
Frequency Range 50~60Hz ± 20% (Auto Sensing)
Power Factor ≥ 0.99
THDi ≤ 3%
OUTPUT
Output Voltage, Regulation 220V / 230V / 240V AC (L+N) ± 1% 380V / 400V /15V AC (3Ph+N)
Power Factor 1.0 for 4/6/10kVA module , 0.9 for 12kVA module
Frequency Range Auto Sensing 50 / 60 Hz ± 1~10% Sync Mode (Configurable), 50 / 60 Hz ±0.1Hz Battery Mode
Crest Factor 3:1 (max.)
Harmonic Distortion ≤ 1 %
Transfer Time Zero
Waveform Pure Sinewave
Overload ≤ 125% for 10 min., ≤ 150% for 1 min., > 150% for 200 ms
Efficiency 96.8% Dual Conversion Mode, 99% ECO Mode
BATTERY CHARGER
Nominal Voltage ± 192V (12V x 32 Nos.)
Battery Quantity 32 ~ 40
Typical Recharge Time 8 hours to 90% capacity
Rack with UPS
IP Protection IP20 / IP21 (Optional)
Alarm / Protection Short Circuit, Input Under/Over Voltage, Over Temperature, Over Current,
Over Load, DC Bus Under/Over Voltage and Battery Low
LED / LCD UPS status, Load % / VA / W, Battery level, Input/Output voltage, Discharge timer, and Fault Code
Display 7 inch LCD Display on Rack, 4 inch LCD on each module
STANDARDS
Quality ISO 9001, ISO 14001, ISO 27001, ISO 50001, RoHS
Safety IEC/EN62040-1
EMC/ Performance IEC/EN62040-2; IEC/EN62040-3, Complying to CE
PHYSICAL
UPS
Module
Dimension 615x418x132 (WxDxH mm) (3U)
Weight 22 Kgs
ENVIRONMENT
Temperature Operating: 0 ~ 50°C*, Storage: -10 ~ 55°C
Humidity / Altitude 0-95% RH Non-condensing / <1500 m
Noise <55dBA
COMMUNICATION
Standard RS232
Optional SNMP / ModBus / Dry Contact / USB / RS485
Monitoring Software NetAgent Utility v5.8 / View Power / UPSilon 2000 / Muser 4000