| Internal Battery Model |
MF1101L3 |
| External Battery Model |
MF1101L2 |
| PHASE |
Single Phase with Groung |
| CAPACITY |
1000VA / 1000W |
| INPUT |
| Nominal Voltage |
208/220/230/240VAC |
| Input Voltage Range |
100-300 VAC at 50% load
160-300 VAC at 100% load
|
| Frequency Range |
40Hz - 70 Hz |
| Power Factor |
≥ 0.99 @ Nominal Voltage (100% load) |
| OUTPUT |
| Output Voltage |
208/220/230/240VAC |
| Voltage Regulation |
± 1% |
| Frequency Range (Synchronized Range) |
47 - 53 Hz or 57 - 63 Hz |
| Frequency Range (Batt. Mode) |
50Hz/60Hz ± 0.1 Hz |
| Current Crest Ratio |
3:1 |
| Harmonic Distortion |
≤ 1% THD (Linear Load) |
Transfer Time |
AC Mode to Battery Mode |
Zero |
| Bypass to Inverter |
4 ms (Typical) |
| Waveform (Batt. Mode) |
Pure Sinewave |
| Efficiency (AC to AC) |
92.0% Dual Conversion Mode, 99.0% ECO Mode |
| BATTERY |
Internal Battery Model |
Battery Type |
12 V / 9 AH |
| Numbers |
2 |
| Typical Recharge Time |
4-6 Hrs recover >90% capacity |
| Charging Current |
1.0 A |
| Charging Voltage |
27.4VDC ± 1V |
External Battery Model |
Battery Type |
SMF VRLA / Lithium Battery Compatible |
| Numbers |
3 |
| Charging Current (max.) |
1.0A/2.0A/4.0A/6.0A |
| Charging Voltage |
41.0VDC ± 1V |
| STATUS INDICATION |
| LCD Panel |
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer and Fault conditions |
| Alarm / Protection |
Short Circuit, Input Under/Over Voltage, Over Temperature, Over Current, Over Load, DC BUS Under / Over Voltage and Battery low |
| PHYSICAL |
Internal Battery Model |
Dimension, D x W x H (mm) |
440 x 325 x 86.5 [2U] |
| Net Weight (kgs) |
12 |
External Battery Model |
Dimension,D x W x H (mm) |
440 x 325 x 86.5 [2U] |
| Net Weight (kgs) |
5.6 |
| ENVIRONMENT |
| Humidity / Altitude / Temperature |
0-95% RH (Non-condensing) / 1500M / Operating: 0-50°C & Storage: -15°C-60°C |
| Noise Level |
Less than 50dB @ 1 Meter |
| STANDARDS |
| Quality |
ISO 90001, ISO 14001, ISO 27001, ISO 45001, ISO 50001, BIS, RoHS |
| Safety |
IEC/EN62040-1; Conformity to IEC / EN |
| EMC / Performance |
IEC/EN62040-2; IEC/EN62040-3, Complying to CE |
| MANAGEMENT |
| Smart RS-232 / USB / IoT |
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC, IoT enable |
| Optional SNMP |
Power management from SNMP manager and web browser |