| MODEL |
MP1104B16 |
MP1105B16 |
MP1106B16 |
MP1104L16 |
MP1105L16 |
MP1106L16 |
MP1111L16-E6 |
| PHASE |
Single Phase with Ground |
| CAPACITY |
4kVA/kW |
5kVA/kW |
6kVA/kW |
4kVA/kW |
5kVA/kW |
6kVA/kW |
11kVA/kW |
| INPUT |
| Nominal Voltage |
208/220/230/240VAC |
| Input Voltage Range |
110-286VAC |
| Frequency Range |
46Hz - 54 Hz or 56Hz - 64 Hz |
| Power Factor |
≥ 0.99 |
| OUTPUT |
| Output Voltage |
208/220/230/240VAC |
| Voltage Regulation |
± 1% |
| Frequency Range (Synchronized Range) |
40-70Hz |
| Frequency Range (Batt. Mode) |
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
| Current Crest Ratio |
3:1 |
| Harmonic Distortion |
≤ 2 % THD (Linear Load); ≤ 5 % THD (Nonlinear Load) |
Transfer Time |
AC Mode to Battery Mode |
0 ms |
| Inverter to Bypass |
0 ms |
| Waveform (Batt. Mode) |
Pure Sinewave |
| Efficiency (AC to AC) |
≥ 94% |
| BATTERY |
| Battery Type |
12 V / 9 AH |
Depending on applications |
| Numbers |
16 |
16/18/20 pcs (Adjustable), ±96, ±108, ±120V DC |
| Typical Recharge Time |
6 Hrs recover >90% capacity |
6-8 Hrs recover >90% capacity |
| Charging Current |
1A (Adjustable) |
4A (Standard) & 10A (Optional) |
| Charging Voltage |
218.4VDC ±1V |
13.65 x N (N = Number of batteries) |
| STATUS INDICATION |
| LCD Panel |
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer and Fault conditions |
| Audible Alarm |
Battery Mode, Low Battery, Overload, Fault |
| PHYSICAL |
| Dimension, D x W x H (mm) |
440 x 625 x 177 (4U) |
440 x 625 x 86.5 (2U) |
| Net Weight (kgs) |
48 |
16 |
18 |
| ENVIRONMENT |
| Humidity |
0-95 % RH @ 0-50°C (non-condensing) |
| Noise Level |
Less than 55dB @ 1 Meter |
Less than 58dB @ 1 Meter |
| MANAGEMENT |
| Smart RS-232 / USB / IoT |
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC, IoT enable |
| SNMP (Optional) |
Power management from SNMP manager and web browser |