GTX Series 120~300kVA

True Online double-conversion with DSP control IGBT based PWM Rectifier and Inverter

Submit Your Enquiry & Our Experts Will Assist You

Thank you! Your submission has been received!
Oops! Something went wrong while submitting the form.
Features:
  • True Online double-conversion with DSP control
  • IGBT based PWM Rectifier and Inverter
  • High input power factor (>0.99)
  • Generator compatible ; Built-in Static Bypass & Manual Bypass
  • Inbuilt galvanic isolation transformer
  • Independent control on three inverter phases
  • High instantaneous overload capacity
  • High MTBF (> 200,000Hrs) and Low MTTR
  • Intelligent self-diagnosing function, all kinds of failure protection, large capability of history records storage
  • Standard emergency power off (EPO)
  • N+X redundancy parallel up to 6 units (Optional)

MODEL GTX33120L50 GTX33160L50 GTX33200L50 GTX33250L50 GTX33300L50
Capacity (kVA) 120 160 200 250 300
INPUT
Rated Voltage 380V / 400V /415V AC (3Ph+N+PE)
Voltage Range 304 ~ 346 V (Derating 10%), 346 ~ 456 V (full load)
Rated Frequency 50 / 60 Hz (Auto Sensing)
Frequency Range 50 /60 Hz ± 10 Hz
Power Factor ≥ 0.99
Harmonic Distortion (THDi) ≤ 3%
Bypass Voltage Range ± 20% (Configurable)
Power Walk-in 10 sec (1 ~ 300 settable)
OUTPUT
Rated Voltage 380V / 400V / 415V AC (3Ph+N+PE)
Voltage Regulation ±1%
Frequency 50 / 60 Hz ± 0.1% in Battery mode
Power Factor 0.9 0.8 0.9
Waveform Pure Sine-Wave
Crest Factor 3:1
Harmonic Distortion (THDv) ≤ 1%
Efficiency ≥ 94.0% Dual Conversion Mode, 99.0% ECO Mode
Transfer Time&Recovery Time Zero ; Within 20ms
Overload Capability ≤110% for 60 Min, ≤125% for 10 Min, ≤150% for 1 Min and ≥ 150% for 300 ms
BATTERY
Nominal DC Voltage 600V DC( Standard ) : Other Configuration as 576V DC & 624V DC
Number of Battery 48 ~ 52 Nos. (Configurable)
Charging Three-Stage Charging, Auto Switch Floating / Equalizing Charge
SYSTEM FEATURES
IP Rating IP20
Alarms / Protection Input Under/Over Voltage, Battery Low, Output Under/Over Voltage, Overload, Short Circuit, Overcharge/discharge & UPS Fault
LED Indications Status for Normal, UPS Fault, Bypass & Battery Mode
LCD Display Input, Bypass, Inverter, Output Voltage & Frequency / Current / kVA / kW / PF / Load %,
Battery Voltage, DC Bus Voltage, Charging & Discharging Current, Temperature and Events
ENVIRONMENTAL
Temperature Operating: 0~50°C*, Storage: -15°C ~ 60°C
Humidity / Altitude 0~95% RH Non-condensing / <1500 M
Noise <75dB @1 meter distance
STANDARDS
Quality ISO 9001, ISO 14001, ISO 27001, ISO 45001, ISO 50001, RoHS
Safety IEC/EN62040-1
EMC / Performance IEC/EN62040-2; IEC/EN62040-3, Complying to CE
PHYSICAL
Dimensions WxDxH (mm) 800 x 800 x 1800 765 x 845 x 1700 1210 x 860 x 1950
Pkd. Dimensions WxDxH (mm) 900 x 900 x 2050 850 x 950 x 2000 1300 x 1000 x 2200
Net Weight (Kg) 680 745 1135 1275 1355
Gross Weight (Kg) 730 795 1200 1340 1420
COMMUNICATION INTERFACE
Standard RS-232 / RS-485
Optional SNMP / ModBus / Dry Contact
Monitoring Software NetAgent Utility v5.8 / View Power / UPSilon 2000 / Muser 4000