| MODULE |
PS75M33375 |
| Dimension WxDxH (mm) |
442 x 628 x 172, 4U |
| Weight (Kg) Each 75kVA |
45 Kg |
| INPUT |
| Nominal Voltage |
380V / 400V / 415V AC (3Ph+N+PE) |
| Operating Voltage Range |
132V - 276V AC (Phase to Neutral) for 100% Load & 132V - 176V AC (Phase to Neutral) for 100% Load
|
| Operating Frequency Range |
50/60Hz ± 10% |
| Power Factor |
≥ 0.99 |
| Harmonic Distortion (THDi) |
≤ 3% |
| Generator Input / Walking |
Support |
| OUTPUT |
| Output Voltage |
380V / 400V / 415V AC (3Ph+N+PE) |
| Voltage Regulation |
± 1% |
| Power Factor |
1.0 (Unity) |
| Frequency |
Auto Sensing 50 / 60 Hz ± 3Hz Sync Mode (Configurable), 50/60 Hz ± 0.1 Hz (Free Running / Self Clocked Mode)
|
| Crest Factor |
3:1 |
| Harmonic Distortion (THDv) |
≤ 1% |
| Over Load |
≤110% for 60 min, ≤125 % for 10 min, ≤ 150% for 1 min, > 150% for 200 ms
|
| Slew Rate |
1 Hz/s |
| Phase Displacement Angle |
120° ± 1° (At 100% Balanced Load) & 120° ± 2° (At 100% Balanced Load)
|
| Transient Response & Response time |
0% to 90 % step load = +/- 5%, < 10 ms (Asynchronized Mode)
|
| Efficiency |
97.1% Dual Conversion Mode, 98.4% EHS Mode, 99.0% ECO Mode
|
| BATTERY |
| Battery Voltage |
± 240V DC Nominal (32 - 44 Nos. Configurable) |
| Charging Current |
15A |
| SYSTEM FEATURE |
| Self-Diagnostics |
During Power ON and Software Control |
| EPO |
UPS Shut down |
| Transfer Time |
Zero |
| Alarm / Protections |
Short Circuit, Input Under/Over Voltage, Over Temperature, Over Load, DC BUS Under / Over Voltage and Battery low
|
| Event Logging & Statistical Data |
16,384 events on LCD: Over temp, DC Bus Fail, Fan Fail, Fuse Fail, Overload, Short- circuit, Device Fail, Inverter Fail, Rectifier Fail, Bypass Fail, etc
|
| Display |
Touch Screen LCD & LED Indication |
| ENVIRONMENTAL |
| Temperature |
Operating: 0~50°C; Storage:-25°C ~ 70°C
|
| Humidity / Altitude |
0~95% RH Non-condensing / <1500 M (above sea level) without derating, Derating 1% for each additional 100m.
|
| Noise |
<65dBA |
| STANDARDS |
| Quality |
ISO 9001, ISO 14001, ISO 27001, ISO 50001, RoHS
|
| Safety |
IEC/EN62040-1 |
| EMC / Performance |
Complying to CE, IEC/EN62040-2; IEC/EN62040-3
|
| COMMUNICATION INTERFACE |
| Standard |
Rack RS232, RS485, Dry Contact
|
| Optional |
BMS / RS485 / USB / SNMP / ModBus / Dry Contact
|
| Monitoring Software |
NetAgent Utility v5.8 / Muser 4000 / Power Manager
|