GTP Series 10~40kVA

True online double-conversion UPS with 3-level IGBT design, wide voltage/frequency range, high input/output power factor, low harmonic distortion (<3%), parallel up to 4 units, configurable batteries (16–50), transformer & IoT compatible.

Submit Your Enquiry & Our Experts Will Assist You

Thank you! Your submission has been received!
Oops! Something went wrong while submitting the form.
Features:
  • True Online Double Conversion Topology
  • 3-Level IGBT Based Rectifier & Inverter
  • Wide Input Voltage Range
  • High Input Power Factor : ≥ 0.99
  • Wide Input Frequency Range : 40-70Hz
  • Parallel upto 4 units
  • Static Bypass and Cold Start
  • High Output Power Factor : 0.9 & Configurable to 1.0
  • Low Harmonic Distortion : <3%
  • Configurable Batteries : 16~20 Nos. (For 10-30kVA) & 30~50 Nos. (For 30 & 40kVA)
  • Transformer Compatible
  • IOT Compatible
MODEL GTP3310L20 GTP3320L20 GTP3330L32 GTP3340L32
Capacity (kVA) 10 20 30 40
INPUT
Nominal Voltage 380V / 400V / 415V AC (3Ph+N+PE)
Voltage Range 228 - 478V AC
Frequency Range 50 / 60 Hz ± 10% Auto Sensing
Power Factor ≥ 0.99
Harmonic Distortion (THDi) ≤ 3%
Bypass
Range
Voltage 380 V AC Max. Voltage: +25% (Optional +10%, +15%, +20%)
400V AC Max. Voltage: +20% (Optional +10%, +15%)
415V AC Max. Voltage: +15% (Optional +10%)
Min. Voltage: -45% (Optional -20%, -30%)
Frequency ± 10% (Configurable)
Generator Input Support
OUTPUT
Output Voltage 380V / 400V / 415V AC (3Ph+N+PE)
Voltage Regulation ± 1%
Power Factor 0.9 Standard / Unity Optional
Frequency Auto Sensing 50 / 60 Hz ± 1~10% Sync Mode (Configurable), 50/60 Hz ± 0.1 Hz Battery Mode
Crest Factor 3:1
Harmonic Distortion (THDv) ≤ 1%
Overload ≤ 125% for 10 Min, ≤ 150% for 1 Min, ≥ 150% for 200 ms
Efficiency 96.5% Dual Conversion Mode, 99.0% ECO Mode
BATTERY
Battery Voltage 192 - 240 VDC 360 - 600 VDC
SYSTEM FEATURES
Transfer Time Zero
Self-Diagnostics / EPO Upon Power On and Software Control / Inbuilt
IP Protection IP20
Alarm / Protection Line Failure, Battery Low, Overload, System Fault and Short Circuit
Display LED Line Mode, Bypass Mode, Battery Low, Overload and UPS Fault Codes
LCD Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load %, Battery Voltage & Temperature, Output W/VA
Parallel Inbuilt
ENVIRONMENT
Temperature Operating: 0~50°C*, Storage: -25°C ~ 55°C
Humidity / Altitude 0~95% RH Non-condensing / <1500 M
Noise <60dBA
STANDARDS
Quality ISO 9001, ISO 14001, ISO 27001, ISO 45001, ISO 50001, RoHS
Safety IEC/EN62040-1
EMC / Performance IEC/EN62040-2; IEC/EN62040-3, Complying to CE
PHYSICAL
Dimension WxDxH (mm) 250x580x655
Net Weight (Kg) 36 40 44 47
COMMUNICATION INTERFACE
Standard RS232
Optional SNMP / ModBus / Dry Contact / USB / RS485
Monitoring Software NetAgent Utility v5.8 / View Power / UPSilon 2000 / Muser 4000