Advanced DSP-based True Online UPS with 3-Level IGBT technology. Features wide input voltage/frequency range, low harmonics, high power factor, and flexible 1-Phase & 3-Phase input configurations. Includes hot-swappable modules, emergency shutdown, generator compatibility, and cold start function. Intelligent fan control and active PFC for energy efficiency and extended system life.

Submit Your Enquiry & Our Experts Will Assist You

Thank you! Your submission has been received!
Oops! Something went wrong while submitting the form.
Features:
  • DSP-Based True Online Double Conversion for precise and efficient power control.
  • 3-Level IGBT Rectifier & Inverter for high efficiency and low harmonic distortion.
  • Wide Input Voltage (40-70Hz) & Frequency Range for flexible compatibility.
  • <3% Input Current Harmonics & ≥0.99 Power Factor for improved energy efficiency.
  • Configurable Battery Rack (16/18/20 Nos.) for optimized energy storage.
  • 1-Phase & 3-Phase Input Options, depending on system configuration.
  • Emergency Power Off (EPO) & Generator Compatibility for added reliability.
  • Cold Start & Hot-Swappable Power Modules for easy maintenance and backup power.
  • Intelligent Fan Control to extend fan life and minimize maintenance.
  • Built-in Active Power Factor Correction for improved system efficiency.

RACK MODEL PS15R3MU PS15R5MU
Maximum Number of Modules 3 5
Maximum Capacity Capacity = No. of Modules x kVA of Module, Maximum Capacity = 50kVA
Dimension (WxDxH) in mm 600 x 840 x 1000 600 x 840 x 1400
Weight of Rack (kg) 142 156
POWER MODULE MODEL PS1104L16 PS1106L16 PS1108L16 PS1110L16 PS3112L20 PS3115L20 PS3116L16
Module Capacity (kVA) 4 6 8 10 12 15 16
INPUT
Nominal Voltage For 1 Phase: 220V / 230V / 240V AC (1Ph+N+PE) & For 3 Phase: 380V / 400V / 415V AC (3Ph+N+PE)
Voltage Range 120V~280V AC Load Dependent (Phase - Neutral)
Frequency Range 40-70Hz
Power Factor ≥ 0.99
THDi ≤ 3%
Bypass Voltage Range Max. Voltage: 25% for 220/380V, 20% for 230/400V & 15% for 240/415V
Min. Voltage: -45% (Optional -10%, -20% & -30%)
OUTPUT
Output Voltage, Regulation 220V / 230V / 240V AC (L+N) ± 1%
Power Factor 1.0
Frequency Range Auto Sensing 50 / 60 Hz ± 1~10% Mains Synchronized (Configurable), 50 / 60 Hz ±0.1Hz Battery Mode
Crest Factor 3:1 (max.)
Harmonic Distortion ≤ 2%
Transfer Time Zero
Waveform Pure Sinewave
Overload ≤ 110% for 60 min, ≤125% for 10 min, 150% for 200 ms
Efficiency 96.5% Dual Conversion Mode, 99% ECO Mode
Waveform Pure Sine Wave
BATTERY CHARGER
Battery Quantity 16~20 Nos.
Charging Current (Module) 16A
Rack with UPS
IP Protection IP 20
Alarm / Protection Short Circuit, Input Under/Over Voltage, Over Temperature, Over Current,
Over Load, DC Bus Under/Over Voltage and Battery Low
LED / LCD UPS status, Load % / VA / W, Battery level, Input/Output voltage, Discharge timer, and Fault Code
Display 7 inch LCD Display on rack
STANDARDS
Quality ISO 9001, ISO 14001, ISO 27001, ISO 45001, ISO 50001, RoHS
Safety IEC/EN62040-1
EMC/ Performance IEC/EN62040-2; IEC/EN62040-3, Complying to CE
PHYSICAL
Dimension
W x D x H (mm)    UPS Module
443 x 580 x 131 (3U)
Net Weight (kg)  UPS Module 29
ENVIRONMENT
Temperature Operating: 0 ~ 50°C, Storage: -15 ~ 60°C
Humidity / Altitude 0-95% RH Non-condensing / <1500 m
Noise < 60dBA
COMMUNICATION
Standard RS-232, Battery Temp. Comm, RS-485, Parallel Intelligent slot x 2, Dry Contact
Optional SNMP / ModBus / USB
Monitoring Software NetAgent Utility v5.8 / View Power / UPSilon 2000 / Muser 4000