| MODEL |
PS40M2316 |
PS40M2320 |
PS40M2325 |
PS40M2330 |
PS40M2332 |
PS40M2340 |
| Rating (kVA) |
16 |
20 |
25 |
30 |
32 |
40 |
| Dimension WxDxH (mm) |
440x650x132(3U) |
| Weight (Kg) |
34 |
| INPUT |
| Nominal Voltage |
380V / 400V / 415V AC (3Ph+N+PE) |
| Operating Voltage Range |
228V ~ 480V AC Load Dependent |
| Operating Frequency Range |
40Hz ~ 70Hz, Auto Sensing |
| Power Factor |
≥ 0.99 |
| Harmonic Distortion (THDi) |
≤3% |
| Generator Input / Walking |
Support / 0~40 Sec (Configurable) |
| OUTPUT |
| Output Voltage, Regulation |
380V / 400V / 415V AC (3Ph+N+PE) ± 1% |
| Power Factor |
1.0 Up to 32kVA module, 0.9 for 40kVA module |
| Frequency |
Auto Sensing 50 / 60 Hz ± 1~10% Sync Mode (Configurable), 50/60 Hz ± 0.1 Hz Battery Mode |
| Crest Factor |
3:1 |
| Harmonic Distortion (THDv) |
≤ 1% |
| Overload |
≤125% for 10 min, ≤ 150% for 1 min, > 150% for 200 ms |
| Efficiency |
96.8% Dual Conversion Mode, 99% ECO Mode, 98.4% EHS mode |
| BATTERY |
| Battery Voltage |
± 240V DC (32 - 40, Configurable) |
| SYSTEM FEATURE |
| Transfer Time |
Zero |
| Alarm / Protections |
Short Circuit, Input Under/Over Voltage, Over Temperature, Over Current,
Over Load, DC BUS Under / Over Voltage and Battery low
|
| Short Circuit |
Hold Whole System |
| Display |
LED |
| ENVIRONMENTAL |
| Temperature |
Operating: 0~50°C*, Storage: -10°C ~ 55°C |
| Humidity / Altitude |
0~95% RH Non-condensing / <1500 M |
| Noise Level |
<55dBA |
| STANDARDS |
| Quality |
ISO 9001, ISO 14001, ISO 27001, ISO 50001, RoHS |
| Safety |
IEC/EN62040-1 |
| EMC / Performance |
IEC/EN62040-2; IEC/EN62040-3, Complying to CE, FCC, ROHS |
| COMMUNICATION INTERFACE |
| Standard |
Rack RS232 |
| Optional |
SNMP / ModBus / Dry Contact / Parallel Card / RS485 / Dry Contact |
| Monitoring Software |
NetAgent Utility v5.8 / View Power / UPSilon 2000 / Muser 4000 / Power Manager |